Residential
Lifts |
|
Our Residential Lifts come with a host of standard
features for your safety and convenience. Many other Options are available for you to consider.
| |
Standard features include:
- Smooth and quiet operation through electro-hydraulic
mechanism
- Carries up to 320 kg - that’s 4 adults or 2 adults and
a wheelchair
- Travel speed of up to 0.300 metres per second
- Safety light curtain across entrance
- Emergency stop
- Alarm button
- Telephone with pre-programmed external lines
- Battery backup for automatic lowering and emergency lighting in
case of power failure
- Up to 12 metres (or 3 floors) of travel
- No separate motor room needed
- Shallow 200mm pit in lift shaft
- “Decorwood” veneer with many choices of finishes
- Anti slip floor covering
- 12 months parts and labour warranty
|
|
Options available include:
- Auto opening swing doors with
adjustable hold open timer
- Auto opening stainless steel or epoxy
sliding doors for car and landing
- Customised fitout with designer finishes (incl wood grain, glass
doors and mirrored panels) to match your home décor
- Hands free phone
- Hand rails
- Fire services
- Single phase power
- Key lockable
|
Issues
for Architects when incorporating a Homelift into building plans:
- Dimensions
- Motor Room
- Lift Shaft
- Location of lift
- Openings and Landings - Car entrances/exits can be in a number
of configurations incl in and out same door/in the front, out the
back, and in
the front and out the
side.
- Car and Internal Finishes
COLOURS:
NEW ANTIQUE WHITE,
SILVER GREY,
OYSTER GREY, CLASSIC BEIGE,
BLACK,
CHARCOAL,
CORAL
WOODGRAINS:
SELECT BEECH,
YOUNG BEECH,
RED CHERRY
- Council Approvals
- PDF Brochure
|
Issues for Builders when preparing the site for a Homelift
- Dimensions -
Minimum dimensions
- Lift Motor Room -
The electrical control and hydraulic power pack are usually located
in the shaft alongside the lift tower and is accessible from
the lower floor.
-
Access Door needs to be provided by Builder to the Motor Room
-
If separate motor room to be used, a viewing window into lift
shaft be installed (according to spec provided by Homelift)
- Lift Shaft -
Shaft to be constructed using masonary (block or brick) with
smooth render on “Door wall”.
-
Alternatively, with 6mm CFC inside lining over studwork
(steel or timber) and external lining to architects detail.
-
Shaft ceiling must be minimum of 3000mm above the upper
floor level and covered with safety mesh where it is accessible.
If not, a safety
flapswitch needs to be opened.
-
Shaft must be clear, plumb and square (internally) with
variations not to exceed 12 mm at any point.
- Supports for rail brackets at pit, each floor and top level,
- Divider beams between hoistway at each floor and top level,
for guide rail bracket supports.
- Lifting point at top of shaft – to our specification
- No Plumbing or duct work to be run in shaft.
- Power and Communications -
Power and phone connection to lift tower side of pit. Leave
2-3 metres coiled up ready for Homelift to attach.
-
Three phase power required – 20 amp
- A GPO Outlet to our spec (if required)
- Chasing of necessary electrical conduits into shaft wall
(if applicable)
- Pit -
Normally 200mm deep pit with a reinforced concrete base
to engineers specifications.
-
Walls to be smooth and square, floor to be level, and
kept free of water and debris.
- Openings and Landings -
Builder to Supply and install Lift access Doors
- Builder to complete Framing and Finishing of doorways
up to door track.
- Entrance walls and finished floors are not to be constructed
until door frames and sills are in place.
- All wall and sill supports for openings must be plumb,
and without any protrusions.
- Recesses, supports and patching to accommodate call
button boxes, and signal fixtures (if applicable)
- Options of Auto swing door openers
- Options of Auto opening Sliding Landing doors
- Options of Auto opening Sliding Car Doors
- Entrances to be well lit and free from any trip hazards
- Lift Car and Internal Finishes -
Car is normally 2metres High
- Car Flooring is non slip rubber matting. Other options
available e.g. carpet, tiles etc.
- Car has powder coated ceiling panel with 2 halogen
lights.
- Car made of Galvinised Steel with Decorwood/Laminex
panels these are
- PDF of swatches
- Other options - mirror stainless steel
- What the builder needs to provide -
doors,
door jambs,
door closers
- Installation
- Workcover Approval
- PDF Brochure
|
| |
| |